RKI Instruments, Inc.www.rkiinstruments.com65-2483RKMulti Point DetectorOperator’s ManualPart Number: 71-0206RKRevision: BReleased: 7/18/14
6 • 65-2483RK Multi Point DetectorH2S DetectorThe detector consists of the detector housing body, detector housing cap, cap gasket, rubber boot, spa
65-2483RK Multi Point Detector • 7Junction BoxUse the junction box to install the multi-point detector at a mounting site that is remote from the con
8 • 65-2483RK Multi Point DetectorFigure 5: Outline & Mounting Dimensions 65-2483RK-013/4 NPT HUBS (4X).253.11Oxygen Detector1.102.40LEL(CH4 IR
65-2483RK Multi Point Detector • 9Figure 6: Outline and Mounting Dimensions 65-2483RK-023/4 NPT HUBS (4X).253.11Oxygen Detector1.102.40CO DetectorL
10 • 65-2483RK Multi Point DetectorFigure 7: Outline and Mounting Dimensions 65-2483RK-033/4 NPT HUBS (4X)3.11 max..25LEL(CH4 IR) Detector1.102.403
65-2483RK Multi Point Detector • 11Figure 8: Outline and Mounting Dimensions 65-2483RK-043.11.253/4 NPT HUBS (4X)1.10LEL(CH4 IR) Detector2.403.00CO
12 • 65-2483RK Multi Point DetectorFigure 9: Outline and Mounting Dimensions 65-2483RK-053.11.253/4 NPT HUBS (4X)1.102.40.20 DIA X .45 Slot,(2X) ,mo
65-2483RK Multi Point Detector • 13Figure 10: Outline and Mounting Dimensions 65-2483RK-062. At the mounting site you select, use #10 screws to mount
14 • 65-2483RK Multi Point DetectorWiring the Multi-Point Detector to a ControllerWARNING: Always verify that the power source is OFF before you mak
65-2483RK Multi Point Detector • 15Figure 11: Wiring the 65-2483RK-01 to a ControllerTerminal Stri pOxygen DetectorGreenController H2S TerminalsContr
65-2483RK Multi Point DetectorWARNINGRead and understand this instruction manual before operating detector. Improper use of the detector could result
16 • 65-2483RK Multi Point DetectorFigure 12: Wiring a 65-2483RK-02 to a ControllerGreenBlackWhiteGreenWhiteRedRedTerminal StripController CO Termin
65-2483RK Multi Point Detector • 17Figure 13: Wiring the 65-2483RK-03 to a ControllerRedBlackTerminal Stri pGreenBlackLEL(CH4 IR) DetectorController
18 • 65-2483RK Multi Point DetectorFigure 14: Wiring the 65-2483RK-04 to a ControllerTerminal Stri pBlackLEL(CH4 IR) DetectorController LEL Terminal
65-2483RK Multi Point Detector • 19Figure 15: Wiring the 65-2483RK-05 to a ControllerGreenWhiteRedController OXY TerminalsController LEL TerminalsBla
20 • 65-2483RK Multi Point DetectorFigure 16: Wiring the 65-2483RK-06 to a Controller9. Connect the cable’s drain wire to an available chassis groun
65-2483RK Multi Point Detector • 21Start UpThis section describes procedures to start up the multi-point detector and place the detector into normal
22 • 65-2483RK Multi Point DetectorMaintenanceThis section describes maintenance procedures. It includes preventive maintenance, troubleshooting, an
65-2483RK Multi Point Detector • 23NOTE: Ensure that you are using an appropriate calibration cylinder for the channel you are testing.5. Use the cal
24 • 65-2483RK Multi Point DetectorTroubleshootingThe troubleshooting guide describes symptoms, probable causes, and recommended action for problems
65-2483RK Multi Point Detector • 25Replacing Components of the Multi-Point DetectorThis section includes maintenance procedures for the IR LEL HC det
65-2483RK Multi Point Detector Product WarrantyRKI Instruments, Inc. warrants gas alarm equipment sold by us to be free from defects in materials, wo
26 • 65-2483RK Multi Point Detector6. Make sure the cap gasket is in place and screw the detector housing cap back onto the detector housing body.7.
65-2483RK Multi Point Detector • 27CO DetectorThis section includes a procedure to replace the plug-in sensor, one to replace the charcoal filter, an
28 • 65-2483RK Multi Point Detector11. Turn on or plug in power to the controller.12. Turn on the controller and place into normal operation.Replaci
65-2483RK Multi Point Detector • 296. Install the spacer and rubber boot onto the replacement sensor’s face.7. Carefully plug the replacement sensor
30 • 65-2483RK Multi Point DetectorCalibration FrequencyAlthough there is no particular calibration frequency that is correct for all applications,
65-2483RK Multi Point Detector • 31NOTE: RKI controllers have a minimum hold feature for zero adjustment and a peak hold feature for span adjustment.
32 • 65-2483RK Multi Point Detector4. Store the components of the calibration kit in a safe and convenient place.Calibration, O2 DetectorThis sectio
65-2483RK Multi Point Detector • 335. Set the fresh air reading according to the controller operator’s manual.6. Unscrew the regulator from the zero
34 • 65-2483RK Multi Point Detector65-1025RK Oxygen replacement plug-in sensor65-2423RK-05 H2S replacement detector assembly (includes sensor)65-243
65-2483RK Multi Point DetectorTable of ContentsOverview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
65-2483RK Multi Point Detector • 1OverviewThis manual describes the 65-2483RK multi point direct connect detector. This manual also describes how to
2 • 65-2483RK Multi Point DetectorNOTE: The following symbol on the detector label is a caution to the user to refer to this documentation for insta
65-2483RK Multi Point Detector • 3DescriptionThis section describes the multi-point detector. It consists of the detectors, the terminal strip, and t
4 • 65-2483RK Multi Point DetectorOxygen DetectorThe detector consists of the oxygen sensor, the detector housing body, detector housing cap, and ca
65-2483RK Multi Point Detector • 5CO DetectorThe detector consists of the CO sensor, charcoal filter with rubber boot, detector housing body, detecto