www.rkiinstruments.com65-2495RK/65-2498RKHydrogen Sulfide DetectorOperator’s ManualPart Number: 71-0155RKRevision: P1Released: 8/17/09
65-2495RK/65-2498RK H2S Detector • 10MaintenanceThis section describes maintenance procedures. It includes preventive maintenance, troubleshooting, a
65-2495RK/65-2498RK H2S Detector • 115. Unscrew the calibration cup from the H2S detector. Make sure that you do not loosen the detector housing cap
65-2495RK/65-2498RK H2S Detector • 12Probable causes• The plug-in sensor has been replaced and the shorting jumper has not been removed.• The calibra
65-2495RK/65-2498RK H2S Detector • 136. Carefully plug the replacement sensor into the four-socket pattern that is located in the detector housing bo
65-2495RK/65-2498RK H2S Detector • 14color-coded leads as you remove them.5. Unscrew the detector from the controller conduit hub or junction box con
65-2495RK/65-2498RK H2S Detector • 15WARNING: Not using the recommended calibration cup and sample flowrate will result in an inaccurate calibration.
65-2495RK/65-2498RK H2S Detector • 16the detector housing cap when you unscrew the calibration cup.NOTE: For convenience, leave the regulator and cal
65-2495RK/65-2498RK H2S Detector • 2Product WarrantyRKI Instruments, Inc., warrants gas alarm equipment sold by us to be free from defects in materia
65-2495RK/65-2498RK H2S Detector • 3Table of ContentsOverview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
65-2495RK/65-2498RK H2S Detector • 4OverviewThis manual describes the 65-2498RK hydrogen sulfide (H2S) detector. This manual also describes how to in
65-2495RK/65-2498RK H2S Detector • 5DescriptionThis section describes the components of the 65-2495RK and 65-2498RK detectors. The 65-2498RK includes
65-2495RK/65-2498RK H2S Detector • 6Detector Housing BodyThe detector housing body protects the electronic components within the housing. Use the mou
65-2495RK/65-2498RK H2S Detector • 7NOTE: If your application does not require a specific mounting site, mount the detector at approximately breathin
65-2495RK/65-2498RK H2S Detector • 85. Guide a two-conductor, shielded cable or two wires in conduit through the unused conduit hub of the junction b
65-2495RK/65-2498RK H2S Detector • 9Start UpThis section describes procedures to start up the H2S detector and place the detector into normal operati