RKI Instruments, Inc.www.rkiinstruments.com65-2484RK-06Multi Point DetectorOperator’s ManualPart Number: 71-0233RKRevision: P1Released: 7/20/11

Page 2

6 • 65-2484RK-06 Multi Point DetectorSO2 DetectorThe 65-2300RK-SO2 detector consists of the detector housing body, detector housing cap, splashguard

Page 3 - Product Warranty

65-2484RK-06 Multi Point Detector • 7Junction BoxesUse the junction boxes to install the multi-point detector at a mounting site that is remote from

Page 4 - Table of Contents

8 • 65-2484RK-06 Multi Point DetectorFigure 5: Outline & Mounting Dimensions 65-2484RK-062. At the mounting site you select, use #10 screws to m

Page 5 - Specifications

65-2484RK-06 Multi Point Detector • 9Wiring the Multi-Point Detector to a ControllerWARNING: Always verify that the power source is OFF before you ma

Page 6

10 • 65-2484RK-06 Multi Point DetectorFigure 6: Wiring the 65-2484RK-06 to a ControllerH2SREDBLKBLKWHTGRNOXYBLACKBLUEGREENWHITEREDWHITEGREENBLACKWHI

Page 7 - Description

65-2484RK-06 Multi Point Detector • 119. Connect the cable’s drain wire to an available chassis ground at the controller. RKI controllers typically h

Page 8 - Plug-in Oxygen Sensor

12 • 65-2484RK-06 Multi Point DetectorMaintenanceThis section describes maintenance procedures. It includes preventive maintenance, troubleshooting,

Page 9

65-2484RK-06 Multi Point Detector • 13NOTE: Ensure that you are using an appropriate calibration cylinder for the channel you are testing.5. Use the

Page 10 - Conduit Seal

14 • 65-2484RK-06 Multi Point DetectorTroubleshootingThe troubleshooting guide describes symptoms, probable causes, and recommended action for probl

Page 11 - Installation

65-2484RK-06 Multi Point Detector • 15Replacing Components of the Multi-Point DetectorThis section includes maintenance procedures for the LEL detect

Page 12

65-2484RK-06 Multi Point DetectorWARNINGRead and understand this instruction manual before operating detector. Improper use of the detector could res

Page 13

16 • 65-2484RK-06 Multi Point Detector6. Make sure the cap gasket is in place and screw the detector housing cap back onto the detector housing body

Page 14

65-2484RK-06 Multi Point Detector • 171. Turn off the controller.2. Turn off or unplug power to the controller.3. Unscrew the detector housing cap fr

Page 15 - Start Up

18 • 65-2484RK-06 Multi Point DetectorSO2 DetectorThis section includes a procedure to replace the SO2 sensor and one to replace the entire detector

Page 16 - Maintenance

65-2484RK-06 Multi Point Detector • 197. Connect the detector leads to the terminal block the same way the old detector was wired. See the controller

Page 17 - Performing the response test

20 • 65-2484RK-06 Multi Point Detector1. Screw the calibration cup onto the bottom of the detector you wish to calibrate.NOTE: If you can verify tha

Page 18 - Troubleshooting

65-2484RK-06 Multi Point Detector • 21Returning to Normal Operation1. Unscrew the calibration cup from the detector.NOTE: For convenience, leave regu

Page 19

22 • 65-2484RK-06 Multi Point Detectorcalibration cup.4. Put the controller into its calibration program. See the controller operator’s manual for i

Page 20 - S Sensor

65-2484RK-06 Multi Point Detector • 23Calibration, SO2 DetectorThis section describes how to calibrate the toxic detector. It includes procedures to

Page 21 - S Detector

24 • 65-2484RK-06 Multi Point DetectorSetting the Response Reading 1. Screw the regulator into the calibration gas cylinder.2. Follow the directions

Page 22 - Detector

65-2484RK-06 Multi Point Detector • 25Parts ListTable 5 lists replacement parts and accessories for the multi-point detector.Table 3: Parts ListPart

Page 23 - S, Detectors

65-2484RK-06 Multi Point Detector Product WarrantyRKI Instruments, Inc. warrants gas alarm equipment sold by us to be free from defects in materials,

Page 24 - Setting the Response Reading

26 • 65-2484RK-06 Multi Point Detector81-0090RK-03 Calibration cylinder, 3-gas mix (CH4/ CO/ O2), 103 liter steel81-0151RK-02 Calibration cylinder,

Page 25 - Calibration, O

65-2484RK-06 Multi Point DetectorTable of ContentsOverview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 26 - Returning to Normal Operation

65-2484RK-06 Multi Point Detector • 1OverviewThis manual describes the 65-2484RK-06 multi point direct connect detector. This manual also describes h

Page 27 - Calibration, SO

2 • 65-2484RK-06 Multi Point DetectorNOTE: The following symbol on the detector label is a caution to the user to refer to this documentation for in

Page 28

65-2484RK-06 Multi Point Detector • 3DescriptionThis section describes the multi-point detector. It consists of the detectors, the terminal strips, t

Page 29 - Parts List

4 • 65-2484RK-06 Multi Point DetectorOxygen DetectorThe detector consists of the oxygen sensor, the detector housing body, detector housing cap, and

Page 30

65-2484RK-06 Multi Point Detector • 5H2S DetectorThe detector consists of the H2S sensor, the detector housing body, detector housing cap, and cap ga