www.rkiinstruments.com65-2423RK-05Hydrogen Sulfide DetectorOperator’s ManualPart Number: 71-0126RKRevision: AReleased: 7/18/14
6 • 65-2423RK-05 H2S DetectorStart UpThis section describes procedures to start up the H2S detector and place the detector into normal operation.Intr
65-2423RK-05 H2S Detector • 7MaintenanceThis section describes maintenance procedures. It includes preventive maintenance, troubleshooting, and compo
8 • 65-2423RK-05 H2S DetectorQuarterlyCalibrate the H2S detector as described in “Calibration” on page 11.TroubleshootingThe troubleshooting guide de
65-2423RK-05 H2S Detector • 9Replacing Components of the H2S DetectorThis section includes a procedure to replace the H2S sensor and one to replace t
10 • 65-2423RK-05 H2S Detector5. Unscrew the detector from the controller conduit hub or junction box hub.6. Guide the detector leads of the replacem
65-2423RK-05 H2S Detector • 11CalibrationThis section describes how to calibrate the H2S detector. It includes procedures to prepare for calibration,
12 • 65-2423RK-05 H2S DetectorNOTE: If you do not allow the gas reading decrease below the alarm points, then unwanted alarms may occur.2. Verify tha
65-2423RK-05 H2S DetectorWARNINGRead and understand this instruction manual before operating detector. Improper use of the detector could result in b
65-2423RK-05 H2S DetectorProduct WarrantyRKI Instruments, Inc. warrants gas alarm equipment sold by us to be free from defects in materials, workmans
65-2423RK-05 H2S DetectorTable of ContentsOverview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
65-2423RK-05 H2S Detector • 1OverviewThis manual describes the 65-2423RK-05 hydrogen sulfide (H2S) detector. This manual also describes how to instal
2 • 65-2423RK-05 H2S DetectorDescriptionThis section describes the components of the H2S detector. The detector consists of the detector housing body
65-2423RK-05 H2S Detector • 3InstallationNOTE: Normally, the H2S detector is shipped already installed in one of the bottom conduit hubs of a control
4 • 65-2423RK-05 H2S Detector2. At the monitoring site, mount the detector in one of the following two ways:• Screw the detector’s 3/4” NPT mounting
65-2423RK-05 H2S Detector • 59. Connect the wires to the applicable controller terminal strip. See the controller operator’s manual and the controlle