RKI Instruments, Inc. • 1855 Whipple Rd. • Hayward, CA 94544 • (510) 441-5656 Beacon 100 Gas MonitorOperator’s Manual Part Number: 71-0035RKRevisio
10 • Internal Description Beacon 100 Gas Monitor Operator’s Manualrespond to a fail condition.ALARM 1 lightThe ALARM 1 light is to the left of the di
Beacon 100 Gas Monitor Operator’s Manual Overview • 11Chapter 3: Installation and Start UpOverviewThis chapter describes procedures to mount the Beac
12 • Mounting the Beacon 100 Gas Monitor Beacon 100 Gas Monitor Operator’s ManualMounting the Beacon 100 Gas MonitorPerform the following procedure t
Beacon 100 Gas Monitor Operator’s Manual Mounting the Beacon 100 Gas Monitor • 13Figure 3: Beacon 100 Gas Monitor External Wiring Diagram++24 VDC Out
14 • Wiring the Beacon 100 Gas Monitor Beacon 100 Gas Monitor Operator’s ManualWiring the Beacon 100 Gas MonitorThis section describes procedures to
Beacon 100 Gas Monitor Operator’s Manual Wiring the Beacon 100 Gas Monitor • 15Connecting External AlarmsPerform the following procedure to connect e
16 • Starting Up the Beacon 100 Gas Monitor Beacon 100 Gas Monitor Operator’s ManualStarting Up the Beacon 100 Gas MonitorPerform the following proce
Beacon 100 Gas Monitor Operator’s Manual Overview • 17Chapter 4: OperationOverviewThis chapter describes the Beacon 100 Gas Monitor in normal operati
18 • Alarm Indications Beacon 100 Gas Monitor Operator’s ManualNOTE: You can select normally energized or normally de-energized relays and latching o
Beacon 100 Gas Monitor Operator’s Manual Alarm Indications • 192. After the gas reading falls below the alarm 1 setpoint, press the reset switch to r
2 • Warranty Beacon 100 Gas Monitor Operator’s Manual Warranty RKI Instruments, Inc., warrants gas alarm equipment manufactured by RKI and sold by
20 • Alarm Indications Beacon 100 Gas Monitor Operator’s ManualResponding to an alarm 3 conditionThis section suggests response to an alarm 3 conditi
Beacon 100 Gas Monitor Operator’s Manual Instrument Setup Program • 21Instrument Setup ProgramThis section describes the Instrument Setup program. Yo
22 • Instrument Setup Program Beacon 100 Gas Monitor Operator’s ManualRunning the Instrument Setup ProgramThis section describes how to enter the pro
Beacon 100 Gas Monitor Operator’s Manual Instrument Setup Program • 23NOTE: If alarm 1 is silenced when the alarm logic is set to latching, the alarm
24 • Instrument Setup Program Beacon 100 Gas Monitor Operator’s ManualAlarm Adjustments ScreenIf ENTER is pressed with the cursor in front of ALARM,
Beacon 100 Gas Monitor Operator’s Manual Instrument Setup Program • 25• To update the alarm type setting:1. Use the UP and DOWN buttons to change the
26 • Overview Beacon 100 Gas Monitor Operator’s ManualChapter 5: MaintenanceOverviewThis chapter describes use of the Calibration Program and correct
Beacon 100 Gas Monitor Operator’s Manual Calibration Program • 27NOTE: Once you leave normal operation and enter this screen, if any alarm conditions
28 • Calibration Program Beacon 100 Gas Monitor Operator’s Manual3. Press the ENTER button to perform a zero adjust. The screen will momentarily show
Beacon 100 Gas Monitor Operator’s Manual Preventive Maintenance • 29button to perform a zero adjust. The screen will momentarily show WAIT and then i
Beacon 100 Gas Monitor Operator’s Manual Table of Contents • 3 Table of Contents Chapter 1: Introduction . . . . . . . . . . . . . . . . . . . . .
30 • Troubleshooting Beacon 100 Gas Monitor Operator’s ManualFrequent or Suspect AlarmsSymptoms• The Beacon 100 alerts you to frequent or suspect ala
Beacon 100 Gas Monitor Operator’s Manual Troubleshooting • 31The Buzzer is not Working ProperlySymptoms• The buzzer does not sound an audible alarm w
Beacon 100 Gas Monitor Operator’s Manual Replacing Components • 32Replacing ComponentsThis section describes procedures to replace the fuses. To repl
Beacon 100 Gas Monitor Operator’s Manual Parts List • 33Parts ListThe table below lists the part numbers and descriptions for replacement parts and a
4 • Overview Beacon 100 Gas Monitor Operator’s Manual Chapter 1: Introduction Overview This chapter briefly describes the Beacon 100 Gas Monitor. Th
Beacon 100 Gas Monitor Operator’s Manual Specifications • 5 Specifications Table 1 lists specifications for the Beacon 100 Gas Monitor. Table 1: Spec
6 • Overview Beacon 100 Gas Monitor Operator’s Manual Chapter 2: Description Overview This chapter describes external and internal components of th
Beacon 100 Gas Monitor Operator’s Manual Internal Description • 7 Internal Description This section describes the internal components of the Beacon
8 • Internal Description Beacon 100 Gas Monitor Operator’s ManualFusesThe Beacon 100 includes one AC fuse (0.5 amp) and one DC fuse (1.5 amp).AC fus
Beacon 100 Gas Monitor Operator’s Manual Internal Description • 9NOTE: See the detector head operator’s manual and the Beacon 100 Detector Head Speci